novaPro32 Routel
Routel set-up
14
7000991003 Q2
Sauter Systems
3
Open the ‘501120_001e.bin’ file:-
The parameters displayed are the factory default parameters.
The following parameters have to be set according to your project:-
Project ID
- The ID of your project (e.g. from your BMTL export file or from the registry)
AS Network ID
- The ID of the AS network concerned (e.g. from your BMTL export file or from the
registry)
PC address
- For the Routel islands to work properly, the PC address has to be set to:-
PC-Address=32512+nx4
where n is 0 for the first island of this project, 1 for second and so on.
- If you have more than one Routel on the same island, the PC address for the
second PC (Routel) has to be: the one of the first one + 1, for the third: the one of
the first + 2 ...
- Important: These rules must be strictly observed.